Products
Combined Heat & Power
Generators
CHP generates electricity on site and captures the engine’s waste heat instead of venting it.
Combined heat and power generates electricity on site and captures the engine’s waste heat instead of venting it, recovering it as hot water or steam for space heating, domestic hot water, process loads or absorption cooling. A conventional generator converts roughly 40 % of its fuel into useful output and loses the rest up the stack; a CHP module puts 85 to 90 % of the same fuel to work. The result is lower energy cost, a substantially smaller carbon footprint, and a facility that keeps running when the grid does not. We supply natural gas CHP modules from 400 kW to 2,500 kW electrical, with matched heat recovery and exhaust gas heat exchangers, and we service what we sell. We offer biogas and propane CHP units as well.

| Product Name | Electrical Power (kW) | Thermal Power (MBTU) | Electrical Efficiency | Thermal Efficiency | Combined Efficiency |
|---|---|---|---|---|---|
| gbox 50 plus | 60 | 437 | 33.4% | 71.3% | 104.7% |
| aura 404 | 100 | 603 | 33.8% | 59.7% | 93.5% |
| aura 404 | 135 | 786 | 34.7% | 59.3% | 94.0% |
| aura 406 | 200 | 1015 | 36.6% | 54.4% | 91.0% |
| aura 408 | 280 | 1417 | 36.9% | 54.8% | 91.7% |
| aura 412 | 420 | 2129 | 37.0% | 55.1% | 92.1% |
| agenitor 404b | 100 | 478 | 35.6% | 49.9% | 85.5% |
| agenitor 404c | 115 | 447 | 33.9% | 38.7% | 72.6% |
| agenitor 404c | 180 | 774 | 38.8% | 48.9% | 87.8% |
| agenitor 406 | 200 | 749 | 36.5% | 40.0% | 76.5% |
| agenitor 406 | 275 | 1129 | 39.6% | 47.7% | 87.3% |
| agenitor 408 | 280 | 1,031 | 36.7% | 39.6% | 76.3% |
| agenitor 408 | 400 | 1500 | 41.9% | 46.0% | 88.0% |
| agenitor 412 | 420 | 1549 | 36.4% | 39.3% | 75.8% |
| agenitor 412 | 500 | 2040 | 39.1% | 46.8% | 85.9% |
| avus 500 plus | 600 | 2330 | 39.9% | 45.4% | 85.3% |
| avus 416 plus | 800 | 2896 | 41.0% | 43.5% | 84.4% |
| avus 1000 plus | 1000 | 3608 | 42.3% | 44.7% | 87.0% |
| avus 1000 plus | 1100 | 4363 | 41.0% | 47.7% | 88.6% |
| avus 800e | 997 | 3911 | 41.4% | 47.5% | 88.9% |
| avus 1200e | 1506 | 5384 | 43.9% | 46.0% | 90.0% |
| avus 1600e | 2014 | 7407 | 43.3% | 46.7% | 90.0% |
| avus 2000e | 2518 | 9261 | 43.4% | 46.7% | 90.0% |
Table notes:
- All figures are for natural gas operation and preliminary data for planning purposes only. Final performance is governed by the project-specific technical data sheet for the selected configuration.
- Biogas and propane (LPG) configurations are available on request; output, efficiency and emissions differ from the natural gas ratings shown.
- Efficiencies are stated on the lower heating value (LHV) of the fuel, per standard reference conditions.
- Ratings are at ISO/DIN 3046-1 standard reference conditions — full load, engine in new condition, at the stated media temperatures. Published tolerances are +5 % on fuel consumption and ±8 % on thermal output.
- Figures are 60 Hz / 480 V for the US market.
- Output is subject to project-specific derating for site altitude, intake air temperature and fuel methane number.
- EPA Certification applies to specific ratings, not to the model family. Where the EPA certification is not available, the installation will need a site-specific permitting path.